93
Learning Basic Features
4.2.3.3 Setting a Reference Frequency using Input Current (I2)
You can set and modify a frequency reference using input current at the I2 terminal after
selecting current input at SW4. Set DRV-07 (Frequency reference source) to5 (I2) and
apply 0–20 mA input current to I2.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
07
Frequency
reference source
Freq Ref
Src
5
I2
011
-
IN
01
Frequency at
maximum analog
input
Freq at
100%
60.00
0–Maximum
Frequency
Hz
50
I2 input monitor
I2 Monitor
0.00
0.00–24.00
mA
52
I2 input filter time
constant
I2 Filter
10
010000
ms
53
I2 minimum input
current
I2 Curr x1
4.00
0.00–20.00
mA
54
I2 output at
minimum current
(%)
I2 Perc y1
0.00
0100
%
55
I2 maximum input
current
I2 Curr x2
20.00
0.00–24.00
mA
56
I2 output at
maximum current
(%)
I2 Perc y2
100.00
0.00–100.00
%
61
I2 rotation direction
options
I2 Inverting
0
No
0–1
-
62
I2 Quantizing level
I2
Quantizing
0.04
0.00*, 0.04
10.00
%
* Quantizing is disabled if 0‘ is selected.