Learning Advanced Features
164
Code
Description
7
FieldBus
Communication command via a communication
option card
8
Pulse
TI Pulse input terminal (0-32 kHz Pulse input)
9
E-PID
Output
External PID output
10
V3
V3 analoge input terminal of Extension IO option
When the analog voltage/current input terminal
selection switch (SW2) at the terminal block is set
to I3(current), input 0-20 mA current. If it is set to
V3 (voltage), input 010 V.
11
I3
PID-11 PID Ref Set
A reference value can be entered if the PID reference type (PID-10) is
set to 0 (Keypad)‘.
PID-12 PID
Ref1AuxSrc
Selects the external input source to be used as the reference for a
PID control. If an external input source is selected, the reference is
determined using the input value at the source (set at PID-10) and the
value set at PID-13 PID Ref1AuxMod.
Setting
Function
0
None
Not used
1
V1
-10-10 V input voltage terminal
3
V2
I2 analog input terminal
[If the analog voltage/current input terminal
selection switch (SW4) at the terminal block is set
to I (current), input 0-20 mA current. If it is set to V
(voltage), input 0–10 V]
4
I2
6
Pulse
TI Pulse input terminal (0-32 kHz Pulse input)
7
Int. 485
RS-485 input terminal
8
FieldBus
Communication command via a communication
option card
10
EPID1
Output
External PID 1 Output
11
EPID1
Fdb Val
External PID 1 feedback value
12
V3
V3 analoge input terminal of Extension IO option
When the analog voltage/current input terminal
selection switch (SW2) at the terminal block is set
to I3(current), input 0-20 mA current. If it is set to
V3 (voltage), input 010 V.
13
I3
PID-13 PID Ref1
AuxMod
PID-13 (PID Ref1) provides formulas to calculate the reference 1
value. If PID-12 (PID RefAuxSrc) is set to any other value thanNone,
the final reference 1 value is calculated using the input value at the
source (set at PID-10) and the input value set at PID-12).