165
Learning Advanced Features
Code
Description
Setting
0
M+(G*A)
1
M*(G*A)
2
M/(G*A)
3
M+(M*(G*A))
4
M+G*2*(A-50)
5
M*(G*2*(A-50))
6
M/(G*2*(A-50))
7
M+M*G*2*(A-50)
8
(M-A)^2
9
M^2+A^2
10
MAX(M,A)
11
MIN(M,A)
12
(M+A)/2
13
Square Root(M+A)
M= Value by the source set at PID-10
G= Gain value set at PID-14
A= Value input by the source set at PID-12
PID-14 PID Ref1 Aux
G
Gain value for the formulas provided by PID-13.
PID-20 PID Fdb Src
Selects feedback input for PID control. If the V1 terminal is set as the
PID feedback source (PID F/B Source), the V1 terminal cannot be set
as the PID reference source (PID Ref Source). To set V1 as a
feedback source, change the reference source.
Setting
Function
0
V1
-10-10 V input voltage terminal
2
V2
I2 analog input terminal
[If the analog voltage/current input terminal
selection switch (SW4) at the terminal block is set
to I (current), input 0-20 mA current. If it is set to V
(voltage), input 0–10 V]
3
I2
4
Int. 485
RS-485 input terminal
5
FieldBus
Communication command via a communication
option card
7
Pulse
TI Pulse input terminal (0-32 kHz Pulse input)
8
EPID1
Output
External PID 1 output
9
EPID1
Fdb Val
External PID 1 feedback
PID-21 PID Fdb
AuxSrc
Selects the external input source to be used as the reference for a
PID control. When the external input source is selected, the reference
is determined using the input value at the source (set at PID-10) and