Learning Advanced Features
226
Example of the Time Event operations
If the Time events are set as the parameters below, the inverter operates as illustrated.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
06
Command
Source
Cmd Ref Src
5: Time Event
0–9
-
07
Frequency
command
source
Freq Ref Src
0: KeyPad
011
-
AP3
11
Time Period
1 Start time
Period1 StartT
10: 00
00: 0024: 00
Min
12
Time Period
1 End time
Period1 Stop T
20: 00
00: 0024: 00
Min
13
Time Period
1 Day of the
week
Period1 Day
0110000
00000001111111
14
Time Period
2 Start time
Period2 StartT
12: 00
00: 0024: 00
Min
15
Time Period
2 End time
Period2 Stop T
17: 00
00: 0024: 00
Min
16
Time Period
2 Day of the
week
Period2 Day
00100000
00000001111111
-
70
Time Event
configuration
Time Event En
1: YES
0
No
-
1
Yes
72
Time Event 1
connection
configuration
T-Event1Period
00000000001
000000000001
111111111111
73
Time Event 1
functions
T-Event1Define
1: Fx
0
None
1
Fx
2
Rx
3
Speed-L
4
Speed-M
5
Speed-H

Table of Contents