Learning Advanced Features
MMC Setting Details
Selects the MMC operation settings.
-None : Deactivates MMC function
-Single Ctrl : Activates general MMC function
-Multi Follower : Activates Master Follower as Multi Follower
mode
-Multi Master: Activates Master Follower as Multi Master mode
-Serve Drv: Sets Serve Drv used at Master Follower.
Decides the number of auxiliary motors to use.
Sets the start auxiliary motor.
Indicates the number of the operating auxiliary motors.
AP1-45–46 Aux Priority1–2
Indicates the operating priority of auxiliary motors.
According to setting by users, it can be influenced by Interlock,
AutoChange and operating time
Each four-digit numbers for the parameter mean the auxiliary
motor numbers and indicate the priority of auxiliary motors. In
other words, the most right number of [AP1-45 Aux Priority1]
indicates the priority of Auxiliary motor 1 and the second
number from the right of [AP1-45 Aux Priority1] indicates the
priority of Auxiliary motor 2.
[AP1-45 Aux Priority1]
x x x x
The Priority of
the Aux motor1
The Priority of
the Aux motor4
[AP1-46 Aux Priority2]
x x x x
The Priority of
the Aux motor5
The Priority of
the Aux motor8
When [AP1-48 Aux All Stop] is set to ―No‖ during input to stop
operating, auxiliary motors are turned off at the same time. when
[AP1-48 Aux All Stop] is set to ―YES‖, auxiliary motors are turned
off gradually based on time of [AP1-54 Aux Stop DT].
Sets the operating priority of MMC.
FIFO : Same as On/Off order of auxiliary motors.
FILO: Opposite to On/Off order auxiliary motors.