Learning Advanced Features
Op Time Order : setting automatically according to operating time
of auxiliary motors.
AP1-50 Aux Start Diff
AP1-59 Aux Stop Diff
One of the conditions to turn on and off the next auxiliary motors.
Parameters to set the difference when the difference between
the reference and feedback is more than regular value
AP1-51 Acc Time
AP1-52 Dec Time
Parameters used when AP1-40 is set to ‗Single Ctrl‘
When an auxiliary motor starts or stops, the main motor stops the
PID control, and performs general acceleration and deceleration.
When an auxiliary motor starts, the main motor decelerates to
the auxiliary motor deceleration frequency set at AP1-70–74
(Stop Freq 1–5) based on the deceleration time set at AP1-52
(Dec Time).
When the auxiliary motor stops, the main motor accelerates up to
the auxiliary motor restart frequency set at AP1-61–65 (Start Freq
1–5) based on the acceleration time set at AP1-51 (Acc Time).
AP1-53 Aux Start DT
AP1-54 Aux Stop DT
The auxiliary motors turns on or off after the auxiliary motor stop
delay time or the auxiliary motor restart delay time elapses, or if
the difference between the current reference and the feedback is
greater than the value set at AP1-50 (Actual Pr Diff).
Sets the auxiliary motor start frequency.
Sets the auxiliary motor stop frequency.
Selects auxiliary motor to be used in AP1-96 and AP1-97.
Indicates operating time(day) selected in AP1-95.
Indicates operating time of auxiliary motors selected in AP1-95.
Deletes operating time of auxiliary motors.