RS-485 Communication Features
386
Comm.
Address
Parameter
Scale
Unit
Assigned Content by Bit
Unit Scale
Unit
Unit
0h03A6–
0h03AF
Reserved
Reserved
0h03B0
E-PID 1 Ref
0.1
%
External PID 1 reference
0h03B1
E-PID 1 Fdb
0.1
%
External PID 1 reference
0h03B2
E-PID 1 Unit Scale
Ref
Proc
Unit
Proc
Unit
Unit Scale External PID 1 reference
0h03B3
E-PID 1 Unit Scale
Fdb
Proc
Unit
Proc
Unit
Unit Scale External PID 1 feedback
0h03B4
Reserved
Reserved
0h03B5
E-PID 2 Ref
0.1
%
External PID 2 reference
0h03B6
E-PID 2 Fdb
0.1
%
External PID 2 feedback
0h03B7
E-PID 2 Unit Scale
Ref
Proc
Unit
Proc
Unit
Unit Scale External PID 2 reference
0h03B8
E-PID 2 Unit Scale
Fdb
Proc
Unit
Proc
Unit
Unit Scale External PID 2 feedback
Note
A frequency set via communication using the common area frequency address (0h0380,
0h0005) is not saved even when used with the parameter save function. To save a changed
frequency to use after a power cycle, follow these steps:
1 Set DRV-07 to ‗Keypad-1ā€˜ and select a target frequency.
2 Set the frequency via communication into the parameter area frequency address
(0h1101).
3 Perform the parameter save (0h03E0: '1') before turning off the power. After the
power cycle, the frequency set before turning off the power is displayed.