387
RS-485 Communication Features
7.3.9.3 Inverter Memory Control Area Parameter (Read and Write)
Comm.
Address
Parameter
Scale
Unit
Changeable
During
Running
Function
0h03E0
Save parameters
-
-
X
0: No, 1: Yes
0h03E1
Monitor mode
initialization
-
-
O
0: No, 1: Yes
0h03E2
Parameter initialization
-
-
X
0: No,
1: All Grp
2: DRV Grp
3: BAS Grp
4: ADV Grp
5: CON Grp
6: IN Grp
7: OUT Grp
8: COM Grp
9: PID Grp
10: EPID
Grp
11: AP1
Grp
12: AP2
Grp
13: AP3
Grp
14: PRT
Grp
15: M2 Grp
Setting is
prohibited
during fault
trip
interruption
s.
0h03E3
Display changed
-
-
O
0: No, 1: Yes
0h03E4
Macro Function
Setting
-
-
X
0: BASIC
1: Compressor
2: Supply Fan
3: Exhaust Fan
4: Cooling Tower
5: Circul. Pump
6: Vacuum Pump
7: Constant Torq
0h03E5
Delete all fault history
-
-
O
0: No, 1: Yes
0h03E6
Delete user-
registrated codes
-
-
O
0: No, 1: Yes
0h03E7
Hide parameter mode
0
Hex
O
Write: 09999
Read: 0: Unlock, 1: Lock
0h03E8
Lock parameter mode
0
Hex
O
Write: 09999
Read: 0: Unlock, 1: Lock