Table of Functions
435
Cod
e
Comm.
Addres
s
Name
LCD
Display
Parameter Setting
Initial
Value
Property*
Ref.
18
EPID2
FdbVal
02
0h1602
Analog
output1
gain
AO1
Gain
-1000.0-1000.0
(%)
100.0
O
p.29
9
03
0h1603
Analog
output1
bias
AO1 Bias
-100.0-100.0 (%)
0.0
O
p.29
9
04
0h1604
Analog
output1
filter
AO1
Filter
0–10000 (msec)
5
O
p.29
9
05
0h1605
Analog
constant
output1
AO1
Const %
0.0-100.0 (%)
0.0
O
p.29
9
06
0h1606
Analog
output1
monitor
AO1
Monitor
0.0-1000.0 (%)
0.0
X
p.29
9
07
0h1607
Analog
output2
AO2
Mode
Identical to the
OUT-02 AO1
Mode selected
range
0:
Frequency
O
p.29
9
08
0h1608
Analog
output2
gain
AO2
Gain
-1000.0-1000.0
(%)
100.0
O
p.29
9
09
0h1609
Analog
output2
bias
AO2 Bias
-100.0-100.0 (%)
0.0
O
p.29
9
10
0h160
A
Analog
output2
filter
AO2
Filter
0–10000 (msec)
5
O
p.29
9
11
0h160
B
Analog
constant
output2
AO2
Const %
0.0-100.0 (%)
0.0
O
p.29
9
12
0h160
C
Analog
output2
monitor
AO2
Monitor
0.0-1000.0 (%)
0.0
X
p.29
9
30
0h161
Fault
Trip
bit
000-111
010