3 - 13
3 Operation and Test Run
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
3-1 Operation of Digital Operator
3
3-1-2 Key Operation Method
(6) The extended function parameter number setting is completed.
Precautions for Correct UsePrecautions for Correct Use
If the set parameter number is not listed in the Parameter List, or if the parameter number is
hidden in the Display Selection setting, “A” in the left-end digit (4th digit) is blinking again. Refer
to Display Selection on page 7-78 to check the parameter number and set it again.
(7) Press (Enter key) to display the parameter setting; press / (Increment/Decrement
key) to change the data; and press (Enter key) again to enter the new setting.
To change the parameter setting, follow the steps (1) to (6) in a similar manner.
Regardless of the display mode of the Digital Operator, if you press (Mode key) for 3 seconds or
more, the data of Output Frequency Monitor (d001) is displayed. However, the Digital Operator
continues to display the function mode and extended function mode in sequence as the normal
operation if you press the Mode key for less than 3 seconds.
The parameter number “A029” is selected.
Returning Display to d001