4 - 13
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-1 Group A: Standard Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
A051 DC Injection
Braking Selection
00: Disabled
01: Enabled
02: Enabled (Operates only at set
frequency)
00 Disabled Enabled – 7-38
A052 DC Injection
Braking
Frequency
0.00 to 99.99
100.0 to 400.0
0.50 Disabled Enabled Hz
A053 DC Injection
Braking Delay
Time
0.0 to 5.0 0.0 Disabled Enabled s
A054 DC Injection
Braking Power
Heavy
load
(CT)
0. to 100.
(0.4 to 55 kW)
50 Disabled Enabled %
0. to 80.
(75 to 132 kW)
40 Disabled Enabled %
Light
load
(VT)
0. to 70.
(0.4 to 55 kW)
50 Disabled Enabled %
0. to 50.
(75 to 132 kW)
40 Disabled Enabled %
A055 DC Injection
Braking Time
0.0 to 60.0 0.5 Disabled Enabled s
A056 DC Injection
Braking
Edge/Level
Selection
00: Edge operation
01: Level operation
01 Disabled Enabled –
A057 Startup DC
Injection Braking
Power
Heavy
load
(CT)
0. to 100.
(0.4 to 55 kW)
0. Disabled Enabled %
0. to 80.
(75 to 132 kW)
0. Disabled Enabled %
Light
load
(VT)
0. to 70.
(0.4 to 55 kW)
0. Disabled Enabled %
0. to 50.
(75 to 132 kW)
0. Disabled Enabled %
A058 Startup DC
Injection Braking
Time
0.0 to 60.0 0.0 Disabled Enabled s
A059 DC Injection
Braking Carrier
Frequency
Heavy
load
(CT)
0.5 to 15.0
(0.4 to 55 kW)
5.0 Disabled Enabled kHz
0.5 to 10.0
(75 to 132 kW)
3.0 Disabled Disabled kHz
Light
load
(VT)
0.5 to 12.0
(0.4 to 55 kW)
3.0 Disabled Enabled kHz
0.5 to 8.0
(75 to 132 kW)
3.0 Disabled Disabled kHz