4 - 31
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-3 Group C: Multi-function Terminal Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
C027 MP Selection 00: Output frequency
01: Output current
02:
Output torque (Only in the heavy load mode)
03: Digital output frequency
04: Output voltage
05: Input power
06: Electronic thermal load rate
07: LAD frequency
08: Digital current monitor
09: Motor temperature
10: Cooling fin temperature
12: DriveProgramming (YA (0))
19: Option 1
20: Option 2
00 Disabled Enabled – 7-140
C028 AM Selection 00: Output frequency
01: Output current
02:
Output torque (Only in the heavy load mode)
04: Output voltage
05: Input power
06: Electronic thermal load rate
07: LAD frequency
09: Motor temperature
10: Cooling fin temperature
11: Output torque (signed)
(Only in the heavy load mode)
13: DriveProgramming (YA (1))
19: Option 1
20: Option 2
00 00 Disabled – 7-142
C029 AMI Selection 00: Output frequency
01: Output current
02: Output torque
04: Output voltage
05: Input power
06: Electronic thermal load rate
07: LAD frequency
09: Motor temperature
10: Cooling fin temperature
14: DriveProgramming (YA (2))
00 00 Disabled –
C030 Digital Current
Monitor Reference
Value
Heavy
load
(CT)
0.20 x Rated current to
2.00 x Rated current
(Current value at digital
current monitor output
1,440 Hz)
Rated
current
value
Enabled Enabled A 7-141
Light
load
(VT)
0.20 x Rated current to
1.50 x Rated current
Rated
current
value
Enabled Enabled A