7-1 Monitor Mode (Group d)
7
Use this function to display the real frequency of the motor when a motor with an encoder is connected
to a load and the PG Board (Model: 3G3AX-PG01) is used. This parameter does not depend on the
control method setting.
Note 1 Set the Number of Encoder Pulses (P011) and the 1st/2nd Motor Pole Number (H004/H204) correctly.
2 This parameter does not depend on the 1st Control Method (A044).
Use this function to display the torque command value that is currently input when torque control is
selected for sensor vector control.
The data display LED “%” is lit while the value of d009 is displayed.
Use this function to display the current torque bias amount setting when sensor vector control is
selected.
The data display LED “%” is lit while the value of d010 is displayed.
Real Frequency Monitor [d008]
Parameter No. Function name Data Default data Unit
d008 Real Frequency Monitor
0.00 to 99.99: During forward run
(Displayed in increments of 0.01Hz)
100.0 to 400.0: During forward run
(Displayed in increments of 0.1Hz)
–99.9 to –0.0: During reverse run
(Displayed in increments of 0.1Hz)
–400 to –100: During reverse run
(Displayed in increments of 1 Hz)
–Hz
Torque Reference Monitor [d009]
Parameter No. Function name Data Default data Unit
d009 Torque Reference Monitor
–200. to 200. (Displayed in increments of
1%)
–%
Torque Bias Monitor [d010]
Parameter No. Function name Data Default data Unit
d010 Torque Bias Monitor
–200. to 200. (Displayed in increments of
1%)
–%