7 - 11
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-1 Monitor Mode (Group d)
7
Use this function to monitor the current time only when the inverter is connected with the optional LCD
Digital Operator (Model: 3G3AX-OP05).
This monitor function is not available with the built-in Digital Operator.
(Example)
“05/28 10:16” means May 28, 10 o’clock and 16 minutes.
Use this function to display the current inverter mode.
Use this function to display the number of inverter trips.
This count value will be saved to the inverter’s EEPROM when the power supply is turned OFF.
Current Time Monitor [d031]
Parameter No. Function name Data Default data Unit
d031 Current Time Monitor
mm/dd hh:mm (Month/Day and Hours/
Minutes, 12 characters)
––
Inverter Mode Monitor [d060]
Parameter No. Function name Data Default data Unit
d060 Inverter Mode Monitor
I-C: IM motor heavy load
I-V: IM motor light load
––
Fault Counter [d080]
Parameter No. Function name Data Default data Unit
d080 Fault Counter
0. to 9999. (Displayed in increments of
1time)
1000 to 6553 (Displayed in increments of
10 times)
–time