7 Detailed Functions
7 - 24
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Set the following external analog input (frequency reference):
FV-FC terminal: 0 to 10 V (Voltage input)
FI-FC terminal: 4 to 20 mA (Current input)
FE-FC terminal: –10 to 10 V (Voltage input)
And the output frequency for the volume adjuster on the Digital Operator.
By default, each analog input is set to reach the maximum frequency at 9.8 V or 19.8 mA.
Analog Input (Voltage or Current) Adjustment
Adjustments for FV-FC Terminals
Parameter No. Function name Data Default data Unit
A011 FV Start Frequency
0.00 to 99.99, 100.00 to 400.00
(Set start and end frequencies.)
*1
*1. The inverter operates at 0 to 10 V when both A011 and A012 are set to 0.00.
0.00 Hz
A012 FV End Frequency
A013 FV Start Ratio
0. to FV end ratio
(Set a start ratio relative to an external
frequency reference of 0 to 10 V)
0.
%
A014
*2
*2. To supply an input voltage of 0 to 5 V between the FV and FC terminals, set A014 to 50%.
FV End Ratio
FV Start Ratio to 100.
(Set an end ratio relative to an external
frequency reference of 0 to 10 V)
100.
A015 FV Start Selection
00: Use FV Start Frequency (A011)
01: 0 Hz
01
Related functions A005, A006, C001 to C008, C081, C082
Adjustments for FI-FC Terminals
Parameter No. Function name Data Default data Unit
A101 FI Start Frequency 0.00 to 99.99, 100.00 to 400.00
(Set start and end frequencies.)
*1
*1. The inverter operates at 0 to 10 V when both A101 and A102 are set to 0.00.
0.00 Hz
A102 FI End Frequency
A103 FI Start Ratio
0. to FI End Ratio
(Set a start ratio relative to an external
frequency reference of 4 to 20 mA)
20.
%
A104 FI End Ratio
FI Start Ratio to 100.
(Set an end ratio relative to an external
frequency reference of 4 to 20 mA)
100.
A105 FI Start Selection
00: Use FI Start Frequency (A101)
01: 0 Hz
00
Related functions A005, A006, C001 to C008, C081, C082