7-3 Basic Functions (Group A)
7
• Setting the Multi-function Input S1 to S8 Selection (C001 to C008) to 32 (SF1) to 38 (SF7) enables
the selection of the Multi-step Speed Reference 0 to 7.
• Use the Multi-step Speed Reference 1 to 7 (A021 to A027) to set the frequency for SF1 to SF7.
• For the Multi-step Speed Reference 0, set the Frequency Reference Selection (A001).
To enable the 1st/2nd/3rd Multi-step Speed Reference 0 setting, set A001 to 02 (Digital Operator:
F001).
If this parameter is set to 01 (Control circuit terminal block: Analog input), the frequency reference for
the Multi-step Speed Reference 0 is set via analog input.
Bit Operation
Parameter No. Function name Data Default data Unit
C001 to C008
Multi-function Input S1 to
S8 Selection
32: SF1 (Multi-step speed setting bit 1)
33: SF2 (Multi-step speed setting bit 2)
34: SF3 (Multi-step speed setting bit 3)
35: SF4 (Multi-step speed setting bit 4)
36: SF5 (Multi-step speed setting bit 5)
37: SF6 (Multi-step speed setting bit 6)
38: SF7 (Multi-step speed setting bit 7)
––
CF1
CF2
CF3
Frequency
reference
13
1
5
9
Without determination time (C169)
11
CF4
15
With determination time (C169)
4
Determination time (C169)
Multi-step
speed
SF7 SF6 SF5 SF4 SF3 SF2 SF1
0th OFF OFF OFF OFF OFF OFF OFF
1st ××××××ON
2nd ×××××ONOFF
3rd ××××ONOFFOFF
4th × × × ON OFF OFF OFF
5th × × ON OFF OFF OFF OFF
6th × ON OFF OFF OFF OFF OFF
7th ON OFF OFF OFF OFF OFF OFF
• When several terminals simultaneously turn ON, the bit
with the smallest number has priority.
In the above table, x indicates that a speed is selected