When the jogging function is enabled, jogging operation starts when the RUN command is input.
To enable the jogging function, set the Multi-function Input S1 to S8 Selection (C001 to C008) to 06
(JG: Jogging).
Set the frequency reference for jogging operation in the Jogging Frequency (A038).
Because, in jogging operation, the frequency reference is output instantaneously without acceleration
time, setting a high jogging frequency value may cause an overload or trip error. Be sure to set a
frequency value that does not cause a trip error.
Use the Jogging Stop Selection (A039) to set the jogging stop method and whether to enable or
disable the jogging function during operation.
To perform jogging operation, turn ON the JG terminal and then turn ON the FW or RV terminal.
When the Jogging Stop Selection (A039) is set to 00, 01, or 02, jogging operation will not occur if the
FW signal turns ON first.
Jogging Operation Function (JG)
Parameter No. Function name Data Default data Unit
C001 to C008
Multi-function Input S1 to
S8 Selection
06: JG (Jogging)
A038 Jogging Frequency 0.00, Starting Frequency (b082) to 9.99 6.00 Hz
A039 Jogging Stop Selection
00: Free-run stop/Disabled in operation
01: Deceleration stop/Disabled in
operation
02: DC injection braking stop/Disabled in
operation
*1
03: Free-run stop/Enabled in operation
04: Deceleration stop/Enabled in
operation
05: DC injection braking stop/Enabled in
operation
*1
*1. If the Jogging Stop Selection(A039) is set to 02 or 05, set the DC Injection Braking Selection (A051).
04
*2
*2. The default data was changed from the previous model.
Disabled during Operation
JG input
FW input
RV input
Output
frequency
Turn ON the JG input first.
Jogging operable Jogging not operable
A038
JG input
FW input
Output
frequency
Set frequency
Jogging
frequency