7-3 Basic Functions (Group A)
7
When the Jogging Stop Selection (A039) is set to 03, 04, or 05, jogging operation will occur even if the
FW signal turns ON first.
However, if the JG signal turns OFF first, the motor will make a free-run stop.
• The torque boost function compensates for the voltage drop caused by the primary resistance in the
motor or by wiring to suppress torque reduction at a low speed range.
• To select Automatic torque boost in the 1st/2nd Torque Boost Selection(A041/A241), set the 1st/2nd
Motor Capacity (H003/H203) and the 1st/2nd Motor Pole Number (H004/H204) according to your
motor.
• By factory setting, the automatic torque boost option is selected.
Enabled during Operation
Torque Boost
Parameter No. Function name Data Default data Unit
A041
1st Torque Boost
Selection
00: Manual torque boost
01: Automatic torque boost
01
*2
–
A241
2nd Torque Boost
Selection
*1
A042
1st Manual Torque Boost
Voltage
0.0 to 20.0
(Percentage of Motor Rated Voltage
Selection (A082))
1.0 %
A242
2nd Manual Torque Boost
Voltage
*1
A342
3rd Manual Torque Boost
Voltage
*1
A043
1st Manual Torque Boost
Frequency
0.0 to 50.0
(Percentage of Base Frequency
(A003/A203/A303))
5.0 %
A243
2nd Manual Torque Boost
Frequency
*1
A343
3rd Manual Torque Boost
Frequency
*1
H003 1st Motor Capacity
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/
4.0/5.5/7.5/11.0/15.0/18.5/22/30/37/45/
55/75/90/110/132
Maximum
applicable
motor
capacity
kW
H203
2nd Motor Capacity
*1
H004 1st Motor Pole Number
2/4/6/8/10 4 pole
H204
2nd Motor Pole Number
*1