7 Detailed Functions
7 - 42
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Use this function to set the upper and lower limits of the output frequency. The set limits will be
applied if the input frequency reference is beyond the upper/lower limit(s).
Set the upper limit first. Be sure that the value set in the 1st/2nd Frequency Upper Limit (A061/A261)
must be larger than the value set in the 1st/2nd Frequency Lower Limit (A062/A262).
Set the upper and lower limit values so that they do not exceed the 1st/2nd/3rd Maximum Frequency
(A004/A204/A304).
Set the Output Frequency Setting/Monitor (F001) and the Multi-step Speed Reference 1 to 15 (A021
to A035) whithin the upper and lower limit settings.
The upper/lower limit setting is disabled when 0 Hz is set.
These functions are disabled when the 3rd control is selected.
(a) Edge operation (A056 = 00) (b) Level operation (A056 = 01)
(Example 1-a) (Example 1-b)
(Example 2-a) (Example 2-b)
(Example 3-a) (Example 3-b)
Frequency Limit
FW
DB
Output
frequency
A055
FW
DB
Output
frequency
FW
DB
Output
frequency
A055
FW
DB
Output
frequency
FW
DB
Output
frequency
A055A053
Free running
FW
DB
Output
frequency
A053
Free running