7 - 43
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-3 Basic Functions (Group A)
7
Setting the lower limit causes the inverter to output the frequency set in the 1st/2nd Frequency Lower
Limit (A062/A262) when 0 V or 4 mA is input to the frequency reference via analog input.
When a frequency is input to the auxiliary frequency reference input (voltage reference) terminal FE
via positive/negative analog input, the lower limit on the forward/reverse side is judged as follows.
When RUN Command Selection (A002) is set to 01 (Control circuit terminal block)
Parameter No. Function name Data Default data Unit
A061 1st Frequency Upper Limit
0.00: Disabled (Function not active)
1st Frequency Lower Limit to 1st
Maximum Frequency
0.00 Hz
A261
2nd Frequency Upper
Limit
*1
*1. To enable the switching to the 2nd/3rd control, allocate one of the Multi-function Input S1 to S8 Selection (C001
to C008) to 08 (SET) or 17 (SET3) and turn ON that terminal.
0.00: Disabled (Function not active)
2nd Frequency Lower Limit to 2nd
Maximum Frequency
A062 1st Frequency Lower Limit
0.00: Disabled (Function not active)
Starting Frequency to 1st Frequency
Upper Limit
A262
2nd Frequency Lower
Limit
*1
0.00: Disabled (Function not active)
Starting Frequency to 2nd Frequency
Upper Limit
When Using FV-FC and FI-FC
Note: The analog frequency reference (FV, FI) shows
characteristics with the default data.
When Using FE-FC
Output frequency [Hz]
Max.
frequency
A004/A204
A061
A062
0 V
4 mA
10 V
20 mA
Frequency
reference
Max.
frequency
A004/A204
A061
A062
10 V
-10 V
A062
A061
Max. frequency
A004/A204
Forward
Reverse