7 - 85
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-4 Detailed Functions (Group b)
7
b012
1st Electronic
Thermal Level
0.20 x Heavy-load rated
current to
1.00 x Heavy-load rated
current [A]
0.20 x Light-load rated
current to
1.00 x Light-load rated
current [A]
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Conversion
*1
Conversion
*1
b212
2nd Electronic
Thermal Level
b312
3rd Electronic
Thermal Level
b016
Free-electronic
Thermal
Current 1
0.00 x Heavy-load rated
current to
1.00 x Heavy-load rated
current [A]
0.00 x Light-load rated
current to
1.00 x Light-load rated
current [A]
0.00 [A]
No
switching
Disabled Disabled
b018
Free-electronic
Thermal
Current 2
b020
Free-electronic
Thermal
Current 3
b022
Overload Limit
Level
0.20 x Heavy-load rated
current to
2.00 x Heavy-load rated
current [A]
(0.20 x Heavy-load rated
current to
1.80 x Heavy-load rated
current [A])
0.20 x Light-load rated
current to
1.50 x Light-load rated
current [A]
(0.20 x Light-load rated
current to
1.50 x Light-load rated
current [A])
1.50×
Heavy-load
rated
current [A]
1.20×
Light-load
rated
current [A]
Enabled
Conversion
*1
b025
Overload Limit
Level 2
b028
Frequency
Pull-in Restart
Level
0.20 x Heavy-load rated
current to
2.00 x Heavy-load rated
current [A]
(0.20 x Heavy-load rated
current to
1.80 x Heavy-load rated
current [A])
0.2 x Light-load rated
current to
1.50 x Light-load rated
current [A]
(0.20 x Light-load rated
current to
1.50 x Light-load rated
current [A])
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
b041
Torque Limit 1
(Four-quadrant
Mode Forward
Power
Running)
Percentage of heavy-load
rated current
0. to 200. [%]
(0. to 180. [%])
no: Function disabled
Percentage of light-load
rated current
0. to 150. [%]
(0. to 150. [%])
no: Function disabled
150. [%] 120. [%] Enabled Disabled
b042
Torque Limit 2
(Four-quadrant
Mode Reverse
Regeneration)
b043
Torque Limit 3
(Four-quadrant
Mode Reverse
Power
Running)
b044
Torque Limit 4
(Four-quadrant
Mode Forward
Regeneration)
b083
Carrier
Frequency
0.5 to 15.0 [kHz]
(0.5 to 10.0 [kHz])
0.5 to 12.0 [kHz]
(0.5 to 8.0 [kHz])
5.0 [kHz]
(3.0 [kHz])
3.0 [kHz]
(3.0 [kHz])
Enabled Disabled
C030
Digital Current
Monitor
Reference
Value
0.20 x Heavy-load rated
current to
2.00 x Heavy-load rated
current [A]
0.20 x Light-load rated
current to
1.50 x Light-load rated
current [A]
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
No.
Parameter
name
Setting range Default data
Initialization at
mode switching
Heavy load (CT) Light load (VT)
Heavy
load (CT)
Light load
(VT)
Heavy to
Light
Light to
Heavy