7 Detailed Functions
7 - 86
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Note For each parameter in the above table, the values enclosed in parentheses ( ) represent the setting range/default data
for high-capacity type (75 to 132 kW) Inverters.
Without parentheses ( ), the parameter has the same setting range/default data regardless of the inverter capacity.
C039
Low Current
Detection
Level
0.00 x Heavy-load rated
current to
2.00 x Heavy-load rated
current [A]
(0.00 x Heavy-load rated
current to
1.80 x Heavy-load rated
current [A])
0.00 x Light-load rated
current to
1.50 x Light-load rated
current [A]
(0.00 x Light-load rated
current to
1.50 x Light-load rated
current [A])
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
C041
Overload
Warning Level
0.00 x Heavy-load rated
current to
2.00 x Heavy-load rated
current [A]
(0.00 x Heavy-load rated
current to
1.80 x Heavy-load rated
current [A])
0.00: Function disabled
0.00 x Light-load rated
current to
1.50 x Light-load rated
current [A]
(0.00 x Light-load rated
current to
1.50 x Light-load rated
current [A])
0.00: Function disabled
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
C055
Overtorque
level (Forward
Power
Running)
Percentage of heavy-load
rated current
0. to 200. [%]
(0. to 180. [%])
Percentage of light-load
rated current
0. to 150. [%]
(0. to 150. [%])
100. [%] 100. [%] Enabled Disabled
C056
Overtorque
level (Reverse
Regeneration)
C057
Overtorque
level (Reverse
Power
Running)
C058
Overtorque
level (Forward
Regeneration)
C111
Overload
Warning Level
2
0.00 x Heavy-load rated
current to
2.00 x Heavy-load rated
current [A]
(0.00 x Heavy-load rated
current to
1.80 x Heavy-load rated
current [A])
0.00: Function disabled
0.00 x Light-load rated
current to
1.50 x Light-load rated
current [A]
(0.00 x Light-load rated
current to
1.50 x Light-load rated
current [A])
0.00: Function disabled
Heavy-load
rated
current [A]
Light-load
rated
current [A]
Enabled
Conversion
*1
H003
1st Motor
Capacity
0.2 to 160 [kW]
*2
Setting in steps
No switching
Heavy-load
rated
capacity
[kW]
Light-load
rated
capacity
[kW]
Disabled Disabled
H203
2nd Motor
Capacity
*1. Conversion: The current value will be converted at the ratio of the rated current for the heavy load/light load mode.
(Example) If you change from a light load mode setting of 5A (rated current: 10A) to the heavy load mode (rated current: 8A), the current
value will be converted as follows: Rated current 8A x 50% (5A/10A) = 4A.
*2. Setting in steps: 0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/5.5/7.5/11.0/15.0/18.5/22/30/37/45/55/75/90/110/132/160 [kW] can be selected.
No.
Parameter
name
Setting range Default data
Initialization at
mode switching
Heavy load (CT) Light load (VT)
Heavy
load (CT)
Light load
(VT)
Heavy to
Light
Light to
Heavy