7 Detailed Functions
7 - 110
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
The multi-function input terminals can be set to either NO (Normally open contact) or NC (Normally
closed contact) individually.
Multi-function Input Operation Selection
Parameter No. Function name Data Default data Unit
C011
Multi-function Input S1
Operation Selection
00: NO (Normally open contact)
01: NC (Normally closed contact)
Each multi-function input terminal
S1 to S8 and the terminal FW can
be set individually to either an NO
contact or NC contact input
terminal.
NO contact: ON when closed, OFF
when open
NC contact: ON when open, OFF
when closed
The terminal allocated to 18 (RS:
Reset) cannot be set to NC contact.
Be sure to set NO contact.
00
C012
Multi-function Input S2
Operation Selection
C013
Multi-function Input S3
Operation Selection
C014
Multi-function Input S4
Operation Selection
C015
Multi-function Input S5
Operation Selection
C016
Multi-function Input S6
Operation Selection
C017
Multi-function Input S7
Operation Selection
C018
Multi-function Input S8
Operation Selection
C019
Forward RUN
Command FW
Operation Selection
00
Related functions C001 to C008