7 - 123
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-5 Multi-function Terminal Functions (Group C)
7
Precautions for Correct UsePrecautions for Correct Use
If you switch the control via the terminal SET/SET3 (C001 to C008 = 08/17) with the terminal
AHD ON, the set frequency remains “as is. To switch the control function, turn OFF the
terminal AHD and have the inverter hold the signal again.
Frequent use of this function could shorten the life expectancy of the internal storage element.
Use this function to capture pulses from a pulse train input via one of the multi-function input
terminals.
You can monitor the captured pulses as the total count in the Pulse Counter Monitor (d028).
To use this function, set the Multi-function Input S1 to S8 Selection (C001 to C008) to 74 (PCNT) or
75 (PCC).
The total count value cannot be stored. It will be reset to zero when the power supply is turned off and
then on again or when the inverter is reset.
To clear the total count value, turn ON the terminal to which PCC (pulse counter clear) is allocated.
The resolution of the input pulse frequency can be obtained from the formula shown below. Note,
however, that this applies to pulse input with a duty ratio of 50%.
The inverter cannot capture input pulses at frequencies higher than the specified resolution. It is
recommended that you use a frequency resolution of 100 Hz or less.
For details on input terminal response, refer to Input Terminal Response Time on page 7-140.
(Example) Input terminal response time = 1, Frequency resolution = 125 Hz
Multi-function Pulse Counter (PCNT, PCC)
Parameter No. Function name Data Default data Unit
C001 to C008
Multi-function Input S1
to S8 Selection
74: PCNT (Pulse counter)
75: PCC (Pulse counter clear)
––
Related functions d028
AHD terminal
Analog input value
Frequency reference
ON
Frequency resolution [Hz] = 250/(Input terminal response time set values C160 to C168 + 1)
Input pulse
PCNT
ON
OFF
Input terminal response time
1
23
4
Counter
value
Input pulses are too short and cannot
be captured during this period.