7 Detailed Functions
7 - 124
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Use this function to allocate the functions listed below to the multi-function output P1 to P5 terminals
and the multi-function relay output (MA, MB) terminals.
The multi-function output P1 to P5 terminals are for open collector output and the multi-function relay
output (MA, MB) terminals are for relay output.
Set the desired function in the Multi-function Output P1 to P5 Selection (C021 to C025) and the
Multi-function Relay Output (MA, MB) Function Selection (C026).
These output terminals can be set to either NO (Normally open contact) or NC (Normally closed
contact) in the Multi-function Output P1 to P5 Operation Selection (C031 to C035) and the
Multi-function Relay Output (MA, MB) Operation Selection (C036) independently.
If the alarm code output function is enabled in Alarm Code Selection (C062) (Alarm Code Output
(AC0 to AC3) on page 7-130), some multi-function output settings are disabled.
When C062 is set to 01 (3 bits), the output terminals P1 to P3 are used for alarm code output; when
C062 is set to 02 (4 bits), the output terminals P1 to P4 are used for alarm code output.
Multi-function Output Selection
Parameter No. Data Function name Reference item Page
C021 to C025,
C026
00 RUN: Signal during RUN Signal during RUN 5-61
01 FA1: Constant speed arrival signal
Frequency Arrival Signal 5-61
02 FA2: Set frequency exceeded signal
03 OL: Overload warning Overload Limit/Overload Warning 7-72
04 OD: Excessive PID deviation PID Function 7-45
05 AL: Alarm signal
06 FA3: Set-frequency only signal Frequency Arrival Signal 7-127
07 OTQ: Overtorque/Undertorque signal Overtorque (OTQ) 7-129
08 IP: Signal during power interruption Alarm Output for Power
Interruption/Undervoltage during
Stop
7-64
09 UV: Signal during undervoltage
10 TRQ: Torque limit Torque Limit Function 7-82
11 RNT: RUN time over RUN time over (RNT) 7-76
12 ONT: Power ON time over Power ON time over (ONT) 7-76
13 THM: Electronic thermal warning Electronic Thermal Function 5-18
19 BRK: Brake release
Brake Control Function 7-104
20 BER: Brake error
21 ZS: 0 Hz detection signal 0-Hz Detection Signal 5-63
22 DSE: Excessive speed deviation V2 Control Mode Selection 6-15
23 POK: Position ready Orientation Function 6-53
24 FA4: Set frequency exceeded signal 2
Frequency Arrival Signal 5-61
25 FA5: Set-frequency only signal 2
26 OL2: Overload warning 2 Overload Limit/Overload Warning 7-72
27
FVDc: Analog FV disconnection
detection
Window Comparator
(Disconnection Detection
FVDc/FIDc/FEDc)
7-9228 FIDc: Analog FI disconnection detection
29
FEDc: Analog FE disconnection
detection
31 FBV: PID feedback comparison signal PID Function 7-45
32
NDc: Communications disconnection
detection
Network Error