7 Detailed Functions
7 - 132
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Use these signals to have the inverter internally perform logical operations with output signals.
All output signals can be used as operands.
However, the logic operation outputs, LOG1 to LOG6, OPO, and no (No allocation) (C021 to C025,
C026 = 33 to 38, 63, 255), cannot be used as operands.
Three operators, AND, OR, and XOR, are available.
Logic Output Signal Operator (LOG1 to LOG3)
Parameter No. Function name Data
Default
data
Unit
C021 to C025
Multi-function Output P1
to P5 Selection
33: LOG1 (Logic operation output 1 (C142,
C143, C144))
34: LOG2 (Logic operation output 2 (C145,
C146, C147))
35: LOG3 (Logic operation output 3 (C148,
C149, C150))
36: LOG4 (Logic operation output 4 (C151,
C152, C153))
37: LOG5 (Logic operation output 5 (C154,
C155, C156))
38: LOG6 (Logic operation output 6 (C157,
C158, C159))
––
C026
Multi-function Relay
Output (MA, MB)
Function Selection
05
C142/C145/
C148/C151/
C154/C157
Logic Output Signal 1
Selection 1 to Logic
Output Signal 6
Selection 1
Same as options for C021 to C026 (33
(LOG1), 34 (LOG2), 35 (LOG3), 36 (LOG4),
37 (LOG5), 38 (LOG6), 63 (OPO), and no
(NO) cannot be selected)
00
C143/C146/
C149/C152/
C155/C158
Logic Output Signal 1
Selection 2 to Logic
Output Signal 6
Selection 2
Same as options for C021 to C026 (33
(LOG1), 34 (LOG2), 35 (LOG3), 36 (LOG4),
37 (LOG5), 38 (LOG6), 63 (OPO), and no
(NO) cannot be selected)
00
C144/C147/
C150/C153/
C156/C159
Logic Output Signal 1
Operator Selection to
Logic Output Signal 6
Operator Selection
00: AND
01: OR
02: XOR
00
Output signal 1
Output signal 2
LOG x (AND)
LOG x (OR)
LOG x (XOR)