7 Detailed Functions
7 - 132
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
• Use these signals to have the inverter internally perform logical operations with output signals.
• All output signals can be used as operands.
However, the logic operation outputs, LOG1 to LOG6, OPO, and no (No allocation) (C021 to C025,
C026 = 33 to 38, 63, 255), cannot be used as operands.
• Three operators, AND, OR, and XOR, are available.
Logic Output Signal Operator (LOG1 to LOG3)
Parameter No. Function name Data
Default
data
Unit
C021 to C025
Multi-function Output P1
to P5 Selection
33: LOG1 (Logic operation output 1 (C142,
C143, C144))
34: LOG2 (Logic operation output 2 (C145,
C146, C147))
35: LOG3 (Logic operation output 3 (C148,
C149, C150))
36: LOG4 (Logic operation output 4 (C151,
C152, C153))
37: LOG5 (Logic operation output 5 (C154,
C155, C156))
38: LOG6 (Logic operation output 6 (C157,
C158, C159))
––
C026
Multi-function Relay
Output (MA, MB)
Function Selection
05 –
C142/C145/
C148/C151/
C154/C157
Logic Output Signal 1
Selection 1 to Logic
Output Signal 6
Selection 1
Same as options for C021 to C026 (33
(LOG1), 34 (LOG2), 35 (LOG3), 36 (LOG4),
37 (LOG5), 38 (LOG6), 63 (OPO), and no
(NO) cannot be selected)
00 –
C143/C146/
C149/C152/
C155/C158
Logic Output Signal 1
Selection 2 to Logic
Output Signal 6
Selection 2
Same as options for C021 to C026 (33
(LOG1), 34 (LOG2), 35 (LOG3), 36 (LOG4),
37 (LOG5), 38 (LOG6), 63 (OPO), and no
(NO) cannot be selected)
00 –
C144/C147/
C150/C153/
C156/C159
Logic Output Signal 1
Operator Selection to
Logic Output Signal 6
Operator Selection
00: AND
01: OR
02: XOR
00 –