7 - 133
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-5 Multi-function Terminal Functions (Group C)
7
The required parameters vary depending on the selected logic operation output.
Use the following table as a reference to set the necessary parameters.
(Example) To output the result of the AND operation between RUN (During RUN signal: 00) and FA2
(Set frequency exceeded signal: 02) to the multi-function output terminal P2 as a logic output
operation 1 (LOG1) terminal (C022 = 33)
This signal is enabled only when Modbus communication is selected for RS485 communications.
Set the Multi-function Output P1 to P5 Selection (C021 to C025) or Multi-function Relay Output (MA,
MB) Function Selection (C026) to 32 (NDc) to allocate the desired signal.
If a reception timeout error occurs, this signal is output until the next data is received.
Set the time until the reception timeout in the Communication Error Timeout Time (C077).
For details, refer to Section 8 Communications Functions.
Selected signal Operand 1 selection Operand 2 selection Operator selection
33: LOG1 (Logic operation output 1) C142 C143 C144
34: LOG2 (Logic operation output 2) C145 C146 C147
35: LOG3 (Logic operation output 3) C148 C149 C150
36: LOG4 (Logic operation output 4) C151 C152 C153
37: LOG5 (Logic operation output 5) C154 C155 C156
38: LOG6 (Logic operation output 6) C157 C158 C159
Item Setting
Multi-function Output P2 Selection (C022) 33: LOG1
Logic Output Signal 1 Selection 1 (C142) 00: RUN
Logic Output Signal 1 Selection 2 (C143) 02: FA2
Logic Output Signal 1 Operator Selection (C144) 00: AND
Communication Disconnection Detection Signal (NDc)
Parameter No. Function name Data Default data Unit
C021 to C025
Multi-function Output P1
to P5 Selection
32: NDc (Communications
disconnection detection)
C026
Multi-function Relay
Output (MA, MB)
Function Selection
05
C077
Communication Error
Timeout Time
0.00: Timeout disabled
0.01 to 99.99
0.00 s
External controller
Inverter
Monitor timer
Communication trip time
(C077)
Communication disconnection
detection signal (NDc)