8 Communications Functions
8 - 26
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
*1 The content of communication error is held until a fault reset is input. Fault reset can be executed during operation.
Coil No.
Modbus
coil
spec. No.
Item R/W Description
004A hex 0049 hex CRC error R
1: Error
0: No error
*1
004B hex 004A hex Overrun error R
1: Error
0: No error
*1
004C hex 004B hex Framing error R
1: Error
0: No error
*1
004D hex 004C hex Parity error R
1: Error
0: No error
*1
004E hex 004D hex Checksum error R
1: Error
0: No error
*1
004F hex – Not used –
0050 hex 004F hex
WCFV
(Window Comparator FV)
–
1: ON
0: OFF
0051 hex 0050 hex
WCFI
(Window Comparator FI)
–
1: ON
0: OFF
0052 hex 0051 hex
WCFE
(Window Comparator FE)
–
1: ON
0: OFF
0053 to
0058 hex
0052 to
0057 hex
(Reserved) – –
005 9hex
to
0058 hex
to
Not used R –