8 - 25
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-1 Coil Number List
0039 hex 0038 hex LOG6 (Logic operation output 6) R
1: ON
0: OFF
003A hex 0039 hex WAC (Capacitor life warning signal) R
1: ON
0: OFF
003B hex 003A hex WAF (Cooling fan life warning signal) R
1: ON
0: OFF
003C hex 003B hex FR (Starting contact signal) R
1: ON
0: OFF
003D hex 003C hex OHF (Cooling fin overheat warning) R
1: ON
0: OFF
003E hex 003D hex LOC (Low current signal) R
1: ON
0: OFF
003F hex 003E hex MO1 (General-purpose output 1) R
1: ON
0: OFF
0040 hex 003F hex MO2 (General-purpose output 2) R
1: ON
0: OFF
0041 hex 0040 hex MO3 (General-purpose output 3) R
1: ON
0: OFF
0042 hex 0041 hex MO4 (General-purpose output 4) R
1: ON
0: OFF
0043 hex 0042 hex MO5 (General-purpose output 5) R
1: ON
0: OFF
0044 hex 0043 hex MO6 (General-purpose output 6) R
1: ON
0: OFF
0045 hex 0044 hex IRDY (Operation ready) R
1: ON
0: OFF
0046 hex 0045 hex FWR (Forward run signal) R
1: ON
0: OFF
0047 hex 0046 hex RVR (Reverse run signal) R
1: ON
0: OFF
0048 hex 0047 hex MJA (Fatal fault signal) R
1: ON
0: OFF
0049 hex 0048 hex During data write R
1: Writing
0: Normal
Coil No.
Modbus
coil
spec. No.
Item R/W Description