EasyManua.ls Logo

Omron RX Series - Page 504

Omron RX Series
688 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Communications Functions
8 - 28
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Note 1 The inverter’s rated current is 1,000.
2 When the set value is 10,000 (100.0 s) or more, the value in the second decimal place is ignored.
3 The PID Feedback Value Monitor function (Register No.: 0006 hex) can be written only when the PID Feedback
Selection (A076) is set to 02 (Modbus communication).
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution
0005 hex 0004 hex Inverter Status C R
0: –
1: Stop
2: Deceleration
3: Constant speed
4: Acceleration
5: Forward
6: Reverse
7: Forward to reverse
8: Reverse to forward
9: Forward run start
10: Reverse run start
0006 hex 0005 hex PID Feedback Value Monitor R/W 0 to 10000 0.01 [%]
0007 hex
to
0010 hex
Not used
0011 hex 0010 hex Fault Counter d080 R 0 to 65530 1 [time]
0012 hex 0011 hex Fault Monitor 1 Factor
d081 R
Refer to Inverter Fault Monitor
Factor List on page 8-34.
0013 hex 0012 hex
Fault Monitor 1 Inverter
Status
Refer to Inverter Fault Monitor
Factor List on page 8-34.
0014 hex 0013 hex
Fault Monitor 1 Output
Frequency (HIGH)
0 to 40000 0.01 [Hz]
0015 hex 0014 hex
Fault Monitor 1 Output
Frequency (LOW)
0016 hex 0015 hex
Fault Monitor 1 Output
Current
Output current value at the time
of trip
0.1 [A]
0017 hex 0016 hex
Fault Monitor 1 Main Circuit
DC Voltage
DC input voltage at the time of
trip
1 [V]
0018 hex 0017 hex
Fault Monitor 1 Total RUN
Time (HIGH)
Total RUN time before the trip 1 [h]
0019 hex 0018 hex
Fault Monitor 1 Total RUN
Time (LOW)
001A hex 0019 hex
Fault Monitor 1 Total Power
ON Time (HIGH)
Total power ON time before the
trip
1 [h]
001B hex 001A hex
Fault Monitor 1 Total Power
ON Time (LOW)

Table of Contents

Related product manuals