8 - 29
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-2 Monitor Function/Enter Command
Register List
Note 1 The inverter’s rated current is 1,000.
2 When the set value is 10,000 (100.0 s) or more, the value in the second decimal place is ignored.
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution
001C hex 001B hex Fault Monitor 2 Factor
d082 R
Refer to Inverter Fault Monitor
Factor List on page 8-34.
001D hex 001C hex
Fault Monitor 2 Inverter
Status
Refer to Inverter Fault Monitor
Factor List on page 8-34.
001E hex 001D hex
Fault Monitor 2 Output
Frequency (HIGH)
0 to 40000 0.01 [Hz]
001F hex 001E hex
Fault Monitor 2 Output
Frequency (LOW)
0020 hex 001F hex
Fault Monitor 2 Output
Current
Output current value at the time
of trip
0.1 [A]
0021 hex 0020 hex
Fault Monitor 2 Main Circuit
DC Voltage
DC input voltage at the time of
trip
1 [V]
0022 hex 0021 hex
Fault Monitor 2 Total RUN
Time (HIGH)
Total RUN time before the trip 1 [h]
0023 hex 0022 hex
Fault Monitor 2 Total RUN
Time (LOW)
0024 hex 0023 hex
Fault Monitor 2 Total Power
ON Time (HIGH)
Total power ON time before the
trip
1 [h]
0025 hex 0024 hex
Fault Monitor 2 Total Power
ON Time (LOW)
0026 hex 0025 hex Fault Monitor 3 Factor
d083 R
Refer to Inverter Fault Monitor
Factor List on page 8-34.
0027 hex 0026 hex
Fault Monitor 3 Inverter
Status
Refer to Inverter Fault Monitor
Factor List on page 8-34.
0028 hex 0027 hex
Fault Monitor 3 Output
Frequency (HIGH)
0 to 40000 0.01 [Hz]
0029 hex 0028 hex
Fault Monitor 3 Output
Frequency (LOW)
002A hex 0029 hex
Fault Monitor 3 Output
Current
Output current value at the time
of trip
0.1 [A]
002B hex 002A hex
Fault Monitor 3 Main Circuit
DC Voltage
DC input voltage at the time of
trip
1 [V]
002C hex 002B hex
Fault Monitor 3 Total RUN
Time (HIGH)
Total RUN time before the trip 1 [h]
002D hex 002C hex
Fault Monitor 3 Total RUN
Time (LOW)
002E hex 002D hex
Fault Monitor 3 Total Power
ON Time (HIGH)
Total power ON time before the
trip
1 [h]
002F hex 002E hex
Fault Monitor 3 Total Power
ON Time (LOW)