8 - 31
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-2 Monitor Function/Enter Command
Register List
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution
0044 hex 0043 hex Fault Monitor 6 Factor
d086 R
Refer to Inverter Fault Monitor
Factor List on page 8-34.
–
0045 hex 0044 hex
Fault Monitor 6 Inverter
Status
Refer to Inverter Fault Monitor
Factor List on page 8-34.
–
0046 hex 0045 hex
Fault Monitor 6 Output
Frequency (HIGH)
0 to 40000 0.01 [Hz]
0047 hex 0046 hex
Fault Monitor 6 Output
Frequency (LOW)
0048 hex 0047 hex
Fault Monitor 6 Output
Current
Output current value at the time
of trip
0.1 [A]
0049 hex 0048 hex
Fault Monitor 6 Main Circuit
DC Voltage
DC input voltage at the time of
trip
1 [V]
004A hex 0049 hex
Fault Monitor 6 Total RUN
Time (HIGH)
Total RUN time before the trip 1 [h]
004B hex 004A hex
Fault Monitor 6 Total RUN
Time (LOW)
004C hex 004B hex
Fault Monitor 6 Total Power
ON Time (HIGH)
Total power ON time before the
trip
1 [h]
004D hex 004C hex
Fault Monitor 6 Total Power
ON Time (LOW)
004E hex 004D hex Warning Monitor d090 R Warning code –
004F to
0050 hex
004E to
004F hex
Not used – – –
0051 hex 0050 hex
Fault Monitor 1 Detection
Ye a r
d081 R
Year in which error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0052 hex 0051 hex
Fault Monitor 1 Detection
Date
d081 R
Date (month and day) at which
error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0053 hex 0052 hex
Fault Monitor 1 Detection
Date
d081 R
Time (o’clock and minutes) at
which error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0054 to
0055 hex
0053 to
0054 hex
Not used – – –
0056 hex 0055 hex
Fault Monitor 2 Detection
Ye a r
d082 R
Year in which error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0057 hex 0056 hex
Fault Monitor 2 Detection
Date
d082 R
Date (month and day) at which
error was detected
(Enabled when LCD Digital
Operator is connected)
BCD