8 - 31
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-2 Monitor Function/Enter Command
Register List
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution
0044 hex 0043 hex Fault Monitor 6 Factor
d086 R
Refer to Inverter Fault Monitor
Factor List on page 8-34.
0045 hex 0044 hex
Fault Monitor 6 Inverter
Status
Refer to Inverter Fault Monitor
Factor List on page 8-34.
0046 hex 0045 hex
Fault Monitor 6 Output
Frequency (HIGH)
0 to 40000 0.01 [Hz]
0047 hex 0046 hex
Fault Monitor 6 Output
Frequency (LOW)
0048 hex 0047 hex
Fault Monitor 6 Output
Current
Output current value at the time
of trip
0.1 [A]
0049 hex 0048 hex
Fault Monitor 6 Main Circuit
DC Voltage
DC input voltage at the time of
trip
1 [V]
004A hex 0049 hex
Fault Monitor 6 Total RUN
Time (HIGH)
Total RUN time before the trip 1 [h]
004B hex 004A hex
Fault Monitor 6 Total RUN
Time (LOW)
004C hex 004B hex
Fault Monitor 6 Total Power
ON Time (HIGH)
Total power ON time before the
trip
1 [h]
004D hex 004C hex
Fault Monitor 6 Total Power
ON Time (LOW)
004E hex 004D hex Warning Monitor d090 R Warning code
004F to
0050 hex
004E to
004F hex
Not used
0051 hex 0050 hex
Fault Monitor 1 Detection
Ye a r
d081 R
Year in which error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0052 hex 0051 hex
Fault Monitor 1 Detection
Date
d081 R
Date (month and day) at which
error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0053 hex 0052 hex
Fault Monitor 1 Detection
Date
d081 R
Time (o’clock and minutes) at
which error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0054 to
0055 hex
0053 to
0054 hex
Not used
0056 hex 0055 hex
Fault Monitor 2 Detection
Ye a r
d082 R
Year in which error was detected
(Enabled when LCD Digital
Operator is connected)
BCD
0057 hex 0056 hex
Fault Monitor 2 Detection
Date
d082 R
Date (month and day) at which
error was detected
(Enabled when LCD Digital
Operator is connected)
BCD

Table of Contents