High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-4 Group A/b/C/H/P Register List
1314 hex 1313 hex
Free-electronic Thermal
Frequency 3
b019 R/W
Free-electronic Thermal
Frequency 2 to 400
1 [Hz]
1315 hex 1314 hex
Free-electronic Thermal
Current 3
b020 R/W 0 to Rated current 0.1 [A]
1316 hex 1315 hex Overload Limit Selection b021 R/W
00: Disabled
01: Enabled during acceleration
and constant speed
02: Enabled during constant
speed
03: Enabled during acceleration
and constant speed
(Accelerated during
regeneration)
–
1317 hex 1316 hex Overload Limit Level b022 R/W
200 to 2000 (0.4 to 55 kW)
200 to 1800 (75 to 132 kW)
(In the light mode)
200 to 1500 (0.4 to 132 kW)
0.1 [%]
1318 hex 1317 hex Overload Limit Parameter b023 R/W 10 to 3000 0.01 [s]
1319 hex 1318 hex Overload Limit Selection 2 b024 R/W
00: Disabled
01: Enabled during acceleration
and constant speed
02: Enabled during constant
speed
03: Enabled during acceleration
and constant speed
(Accelerated during
regeneration)
–
131A hex 1319 hex Overload Limit Level 2 b025 R/W
200 to 2000 (0.4 to 55 kW)
200 to 1800 (75 to 132 kW)
(In the light mode)
200 to 1500 (0.4 to 132 kW)
0.1 [%]
131B hex 131A hex Overload Limit Parameter 2 b026 R/W 10 to 3000 0.01 [s]
131C hex 131B hex
Overcurrent Suppression
Selection
b027 R/W
00: Disabled
01: Enabled
–
131D hex 131C hex
Frequency Pull-in Restart
Level
b028 R/W
200 to 2000 (0.4 to 55 kW)
200 to 1800 (75 to 132 kW)
(In the light mode)
200 to 1500 (0.4 to 132 kW)
0.1 [%]
131E hex 131D hex
Frequency Pull-in Restart
Parameter
b029 R/W 10 to 3000 0.01 [s]
131F hex 131E hex
Starting Frequency Selection
at Frequency Pull-in Restart
b030 R/W
00: Frequency at interruption
01: Max. frequency
02: Set frequency
–
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution