8 Communications Functions
8 - 48
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
1320 hex 131F hex Soft Lock Selection b031 R/W
00: Data other than b031 cannot
be changed when terminal
SFT is ON.
01: Data other than b031 and
set frequency cannot be
changed when terminal SFT
is ON.
02: Data other than b031 cannot
be changed.
03: Data other than b031 and
the specified frequency
parameter cannot be
changed.
10: Data can be changed during
RUN.
–
1321 hex – Not used – – – –
1322 hex – Not used – – – –
1323 hex 1322 hex
RUN Time/Power ON Time
Detection Level
b034
(HIGH)
R/W
0 to 65535 1 [10 h]
1324 hex 1323 hex
b034
(LOW)
R/W
1325 hex 1324 hex RUN Direction Limit Selection b035 R/W
00: No direction limit
01: Forward only (Reverse
limited)
02: Reverse only (Forward
limited)
–
1326 hex 1325 hex
Reduced Voltage Startup
Selection
b036 R/W
0: (Reduced voltage startup
time: Short) to 255: (Reduced
voltage startup time: Long)
–
1327 hex 1326 hex Display Selection b037 R/W
00: Complete display
01: Individual display of
functions
02: User setting + b037
03: Data comparison display
04: Basic display
–
1328 hex 1327 hex Initial Screen Selection b038 R/W
00: Screen on which the Enter
key was last pressed
001 to 060: (d001 to d060)
201: F001
202: Do not set.
–
1329 hex 1328 hex
User Parameter Automatic
Setting Function
b039 R/W
00: Disabled
01: Enabled
–
132A hex 1329 hex Torque Limit Selection b040 R/W
00: Four-quadrant separate
setting
01: Terminal switching
02: Analog Input
03: Option 1
04: Option 2
–
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution