8 - 61
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-4 Group A/b/C/H/P Register List
147D hex 147C hex FV Zero Adjustment C121 R/W 0 to 65530 1
147E hex 147D hex FI Zero Adjustment C122 R/W 0 to 65530 1
147F hex 147E hex FE Zero Adjustment C123 R/W 0 to 65530 1
1480 to
1485 hex
– Not used – – – –
1486 hex 1485 hex
Multi-function Output P1 ON
Delay Time
C130 R/W
0 to 1000
0.1 [s]
1487 hex 1486 hex
Multi-function Output P1 OFF
Delay Time
C131 R/W 0.1 [s]
1488 hex 1487 hex
Multi-function Output P2 ON
Delay Time
C132 R/W 0.1 [s]
1489 hex 1488 hex
Multi-function Output P2 OFF
Delay Time
C133 R/W 0.1 [s]
148A hex 1489 hex
Multi-function Output P3 ON
Delay Time
C134 R/W 0.1 [s]
148B hex 148A hex
Multi-function Output P3 OFF
Delay Time
C135 R/W 0.1 [s]
148C hex 148B hex
Multi-function Output P4 ON
Delay Time
C136 R/W 0.1 [s]
148D hex 148C hex
Multi-function Output P4 OFF
Delay Time
C137 R/W 0.1 [s]
148E hex 148D hex
Multi-function Output P5 ON
Delay Time
C138 R/W 0.1 [s]
148F hex 148E hex
Multi-function Output P5 OFF
Delay Time
C139 R/W 0.1 [s]
1490 hex 148F hex
Multi-function Relay Output
ON Delay Time
C140 R/W 0.1 [s]
1491 hex 1490 hex
Multi-function Relay Output
OFF Delay Time
C141 R/W 0.1 [s]
1492 hex 1491 hex
Logic Output Signal 1
Selection 1
C142 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
–
1493 hex 1492 hex
Logic Output Signal 1
Selection 2
C143 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
–
1494 hex 1493 hex
Logic Output Signal 1
Operator Selection
C144 R/W
00: AND
01: OR
02: XOR
–
1495 hex 1494 hex
Logic Output Signal 2
Selection 1
C145 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
–
1496 hex 1495 hex
Logic Output Signal 2
Selection 2
C146 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
–
1497 hex 1496 hex
Logic Output Signal 2
Operator Selection
C147 R/W
00: AND
01: OR
02: XOR
–
1498 hex 1497 hex
Logic Output Signal 3
Selection 1
C148 R/W
Sa
me as C021 to
C026
(except LOG1 to 6, OPO, no)
–
1499 hex 1498 hex
Logic Output Signal 3
Selection 2
C149 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
–
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution