8 Communications Functions
8 - 62
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
149A hex 1499 hex
Logic Output Signal 3
Operator Selection
C150 R/W
00: AND
01: OR
02: XOR
149B hex 149A hex
Logic Output Signal 4
Selection 1
C151 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
149C hex 149B hex
Logic Output Signal 4
Selection 2
C152 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
149D hex 149C hex
Logic Output Signal 4
Operator Selection
C153 R/W
00: AND
01: OR
02: XOR
149E hex 149D hex
Logic Output Signal 5
Selection 1
C154 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
149F hex 149E hex
Logic Output Signal 5
Selection 2
C155 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
14A0 hex 149F hex
Logic Output Signal 5
Operator Selection
C156 R/W
00: AND
01: OR
02: XOR
14A1 hex 14A0 hex
Logic Output Signal 6
Selection 1
C157 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
14A2 hex 14A1 hex
Logic Output Signal 6
Selection 2
C158 R/W
Same as C021 to C026
(except LOG1 to 6, OPO, no)
14A3 hex 14A2 hex
Logic Output Signal 6
Operator Selection
C159 R/W
00: AND
01: OR
02: XOR
14A4 hex 14A3 hex
Multi-function Input S1
Response Time
C160 R/W 0 to 200 (x 2 ms) 1
14A5 hex 14A4 hex
Multi-function Input S2
Response Time
C161 R/W 0 to 200 (x 2 ms) 1
14A6 hex 14A5 hex
Multi-function Input S3
Response Time
C162 R/W 0 to 200 (x 2 ms) 1
14A7 hex 14A6 hex
Multi-function Input S4
Response Time
C163 R/W 0 to 200 (x 2 ms) 1
14A8 hex 14A7 hex
Multi-function Input S5
Response Time
C164 R/W 0 to 200 (x 2 ms) 1
14A9 hex 14A8 hex
Multi-function Input S6
Response Time
C165 R/W 0 to 200 (x 2 ms) 1
14AA hex 14A9 hex
Multi-function Input S7
Response Time
C166 R/W 0 to 200 (x 2 ms) 1
14AB hex 14AA hex
Multi-function Input S8
Response Tim
e
C167 R/W 0 to 200 (x 2 ms) 1
14
AC hex 14AB hex
Forward RUN Command FW
Response Time
C168 R/W 0 to 200 (x 2 ms) 1
14AD hex 14AC hex
Multi-step Speed/Position
Determination Time
C169 R/W 0 to 200 (x 2 ms) 1
14AE to
1500 hex
Not used
1501 hex 1500 hex Auto-tuning Selection H001 R/W
00: Disabled
01: Enabled (No motor rotation)
02: Enabled (Motor rotation)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution