8 - 63
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-4 Group A/b/C/H/P Register List
1502 hex 1501 hex 1st Motor Parameter selection H002 R/W
00: Standard motor parameter
01: Auto-tuning
02: Auto-tuning data (Online
auto-tuning enabled)
–
1503 hex 1502 hex 1st Motor Capacity H003 R/W Refer to page 8-70. –
1504 hex 1503 hex 1st Motor Pole Number H004 R/W
00: 2P
01: 4P
02: 6P
03: 8P
04: 10P
–
1505 hex 1504 hex
1st Speed Response
H005
(HIGH)
R/W
0 to 80000 0.001
1506 hex 1505 hex
H005
(LOW)
R/W
1507 hex 1506 hex 1st Stabilization Parameter H006 R/W 0 to 255 1
1508 to
1514 hex
– Not used – – – –
1515 hex 1514 hex
1st Motor Parameter R1
H020
(HIGH)
R/W
1 to 65535 0.001 [Ω]
1516 hex 1515 hex
H020
(LOW)
R/W
1517 hex 1516 hex
1st Motor Parameter R2
H021
(HIGH)
R/W
1 to 65535 0.001 [Ω]
1518 hex 1517 hex
H021
(LOW)
R/W
1519 hex 1518 hex
1st Motor Parameter L
H022
(HIGH)
R/W
1 to 65535
0.01
[mH]
151A hex 1519 hex
H022
(LOW)
R/W
151B hex 151A hex
1st Motor Parameter Io
H023
(HIGH)
R/W
1 to 65535 0.01 [A]
151C hex 151B hex
H023
(LOW)
R/W
151D hex 151C hex
1st Motor Parameter J
H024
(HIGH)
R/W
1 to 9999000
0.001
[kg/m
2
]
151E hex 151D hex
H024
(LOW)
R/W
151F to
1523 hex
– Not used – – – –
1524 hex 1523 hex
1st Motor Parameter R1
(Auto-tuning Data)
H030
(HIGH)
R/W
1 to 65535 0.001 [Ω]
1525 hex 1524 hex
H030
(LOW)
R/W
1526 hex 1525 hex
1st Motor Parameter R2
(Auto-tuning Data)
H031
(HIGH)
R/W
1 to 65535 0.001 [Ω]
1527 hex 1526 hex
H031
(LOW)
R/W
1528 hex 1527 hex
1st Motor Parameter L
(Auto-tuning Data)
H032
(HIGH)
R/W
1 to 65535
0.01
[mH]
1529 hex 1528 hex
H032
(LOW)
R/W
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution