8 Communications Functions
8 - 66
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
1625 hex 1624 hex Torque Bias Value P037 R/W
–200 to 200 (0.4 to 55 kW)
–180 to 180 (75 to 132 kW)
1 [%]
1626 hex 1625 hex Torque Bias Polarity Selection P038 R/W
00: As per sign
01: Depends on the RUN
direction
1627 hex 1626 hex
Speed Limit Value in Torque
Control (Forward)
P039
(HIGH)
R/W
0 to 1st Maximum Frequency 0.01 [Hz]
1628 hex 1627 hex
P039
(LOW)
R/W
1629 hex 1628 hex
Speed Limit Value in Torque
Control (Reverse)
P040
(HIGH)
R/W
0 to 1st Maximum Frequency 0.01 [Hz]
162A hex 1629 hex
P040
(LOW)
R/W
162B hex Not used
162C hex Not used
162D hex Not used
162E hex 162D hex
Communications Error
Detection Timer Setting
P044 R/W 0 to 9999 0.01 [s]
162F hex 162E hex
Operation Selection at Host
Communications Error
P045 R/W
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run
04: Deceleration stop
1630 hex 162F hex Assembly Instance Number P046 R/W 0 to 20
1631 hex Not used
1632 hex 1631 hex
Operation Selection at Idle
Mode Detection
P048 R/W
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
1633 hex 1632 hex
Number of Poles for Rotation
Speed Setting
P049 R/W
0: 0P
1: 2P
2: 4P
3: 6P
4: 8P
5: 10P
6: 12P
7: 14P
8: 16P
9: 18P
10: 20P
11: 22P
12: 24P
13: 26P
14: 28P
15: 30P
16: 32P
17: 34P
18: 36P
19: 38P
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution