8 - 67
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-5 Modbus Communication Register Number List
8
8-5-4 Group A/b/C/H/P Register List
1634 to
1638 hex
1633 hex Not used – – – –
1639 hex 1638 hex Pulse Train Frequency Scale P055 R/W
10 to 500
* Input frequency at maximum
frequency
0.1 [kHz]
163A hex 1639 hex
Pulse Train Frequency Filter
Time Parameter
P056 R/W 1 to 200 0.01 [s]
163B hex 163A hex
Pulse Train Frequency Bias
Amount
P057 R/W –100 to 100 1 [%]
163C hex 163B hex Pulse Train Frequency Limit P058 R/W 0 to 100 1 [%]
163D hex 163C hex Not used – – – –
163E hex 163D hex
Multi-step Position Command 0
P060
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
163F hex 163E hex
P060
(LOW)
R/W
1640 hex 163F hex
Multi-step Position Command 1
P061
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
1641 hex 1640 hex
P061
(LOW)
R/W
1642 hex 1641 hex
Multi-step Position Command 2
P062
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
1643 hex 1642 hex
P062
(LOW)
R/W
1644 hex 1643 hex
Multi-step Position Command 3
P063
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
1645 hex 1644 hex
P063
(LOW)
R/W
1646 hex 1645 hex
Multi-step Position Command 4
P064
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
1647 hex 1646 hex
P064
(LOW)
R/W
1648 hex 1647 hex
Multi-step Position Command 5
P065
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
1649 hex 1648 hex
P065
(LOW)
R/W
164A hex 1649 hex
Multi-step Position Command 6
P066
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
164B hex 164A hex
P066
(LOW)
R/W
164C hex 164B hex
Multi-step Position Command 7
P067
(HIGH)
R/W
Position range specification
(reverse side) to position range
specification (forward side)
1
164D hex 164C hex
P067
(LOW)
R/W
164E hex 164D hex Origin Search Mode P068 R/W
00: Origin search mode 1
01: Origin search mode 2
02: Origin search mode 3
–
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W Monitor or setting data
Resolution