8 - 89
8 Communications Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
8-6 ASCII Method
8
8-6-2 Communications Commands
* If Data is a selection parameter value, the corresponding code data will be sent/received.
For example, the code data for the data set in the 1st/2nd Motor Capacity (H003/H203) are as follows.
If Data is a numeric value, refer to the function code list.
Example. When the 1st Acceleration Time 1 (F002) is set to 30.00 s, Data is 3000.
Negative response: Refer to page 8-93
Sets a parameter value.
Transmission Frame
Response frame
Positive response: Refer to page 8-92
Negative response: Refer to page 8-93
Code data 00 01 02 03 04 05 06 07 08 09 10
Domestic
(b085 = 00, 02)
0.2 kW 0.4 0.75 1.5 2.2 3.7
Code data 11 12 13 14 15 16 17 18 19 20 21
Domestic
(b085 = 00, 02)
5.5 kW 7.5 11 15 18.5 22 30 37 45 55 75
Code data 22 23 24 25 26
Domestic
(b085 = 00, 02)
90 kW 110 132 150 160
Command 07
Frame format
STX Station No. Command Parameter Data BCC CR
Description Data size Setting
STX Control code (Start of Text) 1 byte STX (0x02)
Station No. Station No. of target Inverter 2 bytes 01 to 32, FF (Broadcast to all stations)
Command Transmission command 2 bytes 07
Parameter Parameter number for data 4 bytes
*1
*1. Parameter can be one of the following parameter groups:
Group F (excluding F001), Group A, Group B, Group C, Group H, Group P (For F001, use command 01.)
Data
Parameter data
(Decimal ASCII code)
8 bytes
*2
*2. Refer to command 06.
BCC Block check code 2 bytes
Exclusive OR of frame segments from
Station No. to Data (Refer to page 8-94.)
CR Control code (Carriage Return) 1 byte CR (0x0D)