8 Communications Functions
8 - 90
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
Restores all parameters to the default datas.
The function of this command depends on the value set in the Initialization Selection (b084). If b084 is
set to 00, the trip data will be cleared.
Transmission Frame
Response frame
Positive response: Refer to page 8-92
Negative response: Refer to page 8-93
Checks if a set value can be stored in EEPROM.
Transmission Frame
Command 08
Frame format
STX Station
No.
Command BCC CR
Description Data size Setting
STX Control code (Start of Text) 1 byte STX (0x02)
Station
No.
Station No. of target Inverter 2 bytes 01 to 32, FF (Broadcast to all stations)
Command
Transmission command 2 bytes 08
BCC Block check code 2 bytes
Exclusive OR of frame segments from
Station No. to Data (Refer to page 8-94.)
CR Control code (Carriage Return) 1 byte CR (0x0D)
Command 09
Frame format
STX
Station
No.
Command BCC CR
Description Data size Setting
STX Control code (Start of Text) 1 byte STX (0x02)
Station
No.
Station No. of target Inverter 2 bytes 01 to 32
Command
Transmission command 2 bytes 09
BCC Block check code 2 bytes
Exclusive OR of frame segments from
Station No. to Data (Refer to page 8-94.)
CR Control code (Carriage Return) 1 byte CR (0x0D)