Table 9: Drive Enclosure power characteristics
Power
characteristic
Value
Maximum
output power
Maximum power consumption depends on the type of Drive
Enclosure (DE2-24P or DE2-24C), its size (2U/4U), and
conguration.
• 4U HDD= 376VA (4TB HDD)
• 2U SFF = 260VA (900GB SFF HDD)
• 2U SSD = 307VA (19 x 1.6TB SSD)
Frequency
50–60 Hz
Voltage range 100–240 Volts AC rated
Maximum range
selection
47–63 Hz
Maximum
inrush current
20A
System Power Requirements
The total power consumed by the Oracle FS1 Flash Storage System is dependent
on the conguration of the system. To determine the system electrical input
ratings for Oracle Flash Storage Systems that use the Oracle supported PDUs,
refer to the PDU information provided for Oracle Flash Storage Systems.
Oracle Flash Storage Systems require redundant input power feeds for proper
fault tolerant operation.
Note: Ensure that you have the exact power load and current requirements for
your specic Oracle FS System at hand.
If non-Oracle PDUs are used, you must determine the electrical input ratings of
the Oracle FS System conguration.
PDU Hardware Specifications
The PDUs used in a not-racked Oracle FS System installation must provide
redundancy for both external AC power source and internal AC power
distribution to the components. The PDUs must provide sucient current to
meet the sum of the requirements for the Oracle FS System components.
Oracle PDUs might be purchased for use with non-Oracle racks. The Oracle FS
System component power cords have been designed to work with vertical style
Oracle or third party PDUs. Non-Oracle PDUs must be compatible with Oracle
component power cord lengths and plug types. Non-Oracle PDUs must be
Oracle FS Systems: Installation Overview
24