Table 11: Low voltage three-phase PDU for Oracle Flash Storage Systems
Low Voltage 3Ph (3W + ground)
kVA size 15 kVA
Marketing part number 7104979
Phase 3
No grounded neutral conductors are
provided in the input cords.
Voltage input
3Ph [(3W+ground)] 208Vac, 50/60 Hz,
maximum. 40A per phase
Can be connected to Ph-Ph input sources in
the range of 190V – 220V AC (nominal)
Number of input cords and plug type
1x IEC 309, 60A (Hubbell C460P9W or
equivalent)
Number of data center receptacles and
type
1x IEC 309, 60A (Hubbell 460R9S or
equivalent)
Maximum input current for each cord 40A
Outlet receptacles (number/type) 42/C13 (seven for each outlet group)
6/C19 (one for each outlet group)
Outlet groups for each PDU 6
PDU power cord length 2 meters (6.6 feet)
PDU power cords are 4 meters (13 feet)
long, but sections are connected for internal
routing in the rack.
Table 12: High voltage single phase PDU for Oracle Flash Storage Systems
High Voltage 1Ph (2W + ground)
kVA size 10 kVA
Marketing part number 7104983
Phase 1
Oracle FS Systems: Installation Overview
26