EasyManua.ls Logo

Sel 751A - Bare-Fiber Sensor Installation; Figure 2.33 Bare-Fiber Sensor Assembly; Figure 2.34 Bare-Fiber Sensor Mounting Example; Figure 2.35 Bare-Fiber Sensor Components (V-Pin Style)

Sel 751A
640 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.33
Date Code 20100129 Instruction Manual SEL-751A Relay
Installation
Arc-Flash Protection: System Installation
Bare-Fiber Sensor
Installation
The bare-fiber sensor is optimized for monitoring of large distributed
resources, such as switchgear system bus enclosures. The bare-fiber sensor is
omnidirectional and can be mounted in close proximity to the switchgear
enclosure walls. Figure 2.33 shows a schematic diagram of the bare-fiber
sensor. Figure 2.34 shows a bare-fiber sensor mounting example photo.
Total loop length = 2 • A + B (allowed range 3 to 70 meters)
Range for A: 1 to 30 meters
Range for B: 1 to 50 meters
Figure 2.33 Bare-Fiber Sensor Assembly
Figure 2.34 Bare-Fiber Sensor Mounting Example
A bare-fiber sensor consists of the major components shown in Figure 2.35.
Two connector options (V-pin and ST) are available for transitioning from the
jacketed to the bare-fiber section as shown in Figure 2.36. The ST connector
option is generally superior because of positive locking and lower coupling
loss.
Figure 2.35 Bare-Fiber Sensor Components (V-Pin Style)
For correct operation, a bare-fiber sensor must be located within 2 m of the
arcing site, with at least 0.5 m of the fiber exposed to the light. The maximum
length of the bare-fiber sensor is limited to 70 m and includes both, bare- and
i8004a
Dual V-Pin
Latch
V-Pin
Terminators
V-Pin or
ST Splice
Connector
A” Meters
“B” Meters
Bare-Fiber
Jacketed-Fiber Zipcord Duplex
Bare-Fiber Sen-
sor Section
Bare-Fiber Transition
Connectors (V-Pin)
Connector Splice
Bushing (V-Pin)
Jacketed-Fiber
Section

Table of Contents

Related product manuals