It is possible to configure several stages for different tasks:
•
Reporting only (with or without fault record)
Use this stage to report 1 or 2 faulty C-elements. To do this, set the parameters Max. no. of def.
elem. phs A, Max. no. of def. elem. phs B , Max. no. of def. elem. phs C , or
Max. no. of def. elem. to a small value (1 or 2). The parameter Operate delay can be set to 0.
If you would like to prevent the operate (tripping) and fault logging (fault log and fault record), set the
parameter Operate & flt.rec. blocked to yes.
If you would like to prevent only the operate (tripping) and the fault logging must occur, remove this
stage from the interface Trip to the circuit breaker (see also 5.4.2 Structure of the Function Group Inter-
faces with Circuit-Breaker Function Group).
•
Indication with delayed operate
Use this stage to report in case of some faulty C-elements and to set a relatively long time delay of the
operate, for example, 2 hours. During this time, the fault of the C-elements can be clarified. If it is
possible to find a solution, the counter status can be reset manually. This way, the stage drops out. If a
solution cannot be found within 2 hours, the stage trips and disconnects the capacitor bank.
•
Immediate operate
The stage is used to initiate the operate immediately after a larger number of C-elements became faulty.
Settings
Addr. Parameter C Setting Options Default Setting
Counter 1
_:16261:1 Counter 1:Mode
•
off
•
on
•
test
off
_:16261:2 Counter 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:16261:101 Counter 1:Type of
counting groups
•
segregated
•
sum
segregated
_:16261:102 Counter 1:Type of
counting phases
•
segregated
•
sum
segregated
_:16261:103 Counter 1:Max. no. of
def. elem. phs A
1 to 1000 10
_:16261:104 Counter 1:Max. no. of
def. elem. phs B
1 to 1000 10
_:16261:105 Counter 1:Max. no. of
def. elem. phs C
1 to 1000 10
_:16261:106 Counter 1:Max. no. of
def. elem.
1 to 1000 10
_:16261:6 Counter 1:Operate delay 0.00 s to 10000.00 s 0.00 s
Information List
No.
Information Data Class
(Type)
Type
Counter 1
_:16261:81 Counter 1:>Block stage SPS I
_:16261:54 Counter 1:Inactive SPS O
_:16261:52 Counter 1:Behavior ENS O
_:16261:53 Counter 1:Health ENS O
_:16261:55 Counter 1:Pickup ACD O
_:16261:56 Counter 1:Operate delay expired ACT O
7.5.5.3
7.5.5.4
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase
1018 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017