EasyManua.ls Logo

Siemens 7SJ85 - Information List

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting
_:572:9 Stage 2:Measured value
VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:572:8 Stage 2:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
_:572:3 Stage 2:Threshold 0.300 V to 340.000 V 65.000 V
_:572:4 Stage 2:Dropout ratio 1.01 to 1.20 1.05
_:572:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s
Information List
No. Information Data Class
(Type)
Type
General
_:2311:500 General:>Current flow-criterion SPS I
_:2311:300 General:Current crit. fulf. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:571:81 Stage 1:>Block stage SPS I
_:571:54 Stage 1:Inactive SPS O
_:571:52 Stage 1:Behavior ENS O
_:571:53 Stage 1:Health ENS O
_:571:55 Stage 1:Pickup ACD O
_:571:56 Stage 1:Operate delay expired ACT O
_:571:57 Stage 1:Operate ACT O
Stage 2
_:572:81 Stage 2:>Block stage SPS I
_:572:54 Stage 2:Inactive SPS O
_:572:52 Stage 2:Behavior ENS O
_:572:53 Stage 2:Health ENS O
_:572:55 Stage 2:Pickup ACD O
_:572:56 Stage 2:Operate delay expired ACT O
_:572:57 Stage 2:Operate ACT O
6.31.6
Protection and Automation Functions
6.31 Undervoltage Protection with Any Voltage
762 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals