Figure 8-25 2-Pole Triggering, Routing in DIGSI
The feedback is routed via the position with the disconnector.
Settings
Addr.
Parameter C Setting Options Default Setting
Control
_:4201:101 Control:Control model
status only
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
SBO w. enh.
security
_:4201:102 Control:SBO time-out 0.01 s to 1800.00 s 30.00 s
_:4201:103 Control:Feedback moni-
toring time
0.01 s to 1800.00 s 10.00 s
_:4201:104 Control:Check switching
authority
no
yes
yes
_:4201:105 Control:Check if pos. is
reached
no
yes
yes
_:4201:106 Control:Check double
activat. blk.
no
yes
yes
Disconnector
_:5401:101 Disconnector:Maximum
output time
0.01 s to 1800.00 s 10.00 s
_:5401:102 Disconnector:Seal-in time 0.00 s to 60.00 s 0.00 s
_:5401:103 Disconnector:Switching-
device type
switch-disconnector
disconnector
grounding switch
fast grounding switch
disconnector
8.2.3.4
Control Functions
8.2 Switching Devices
SIPROTEC 5, Overcurrent Protection, Manual 1103
C53000-G5040-C017-8, Edition 07.2017