EasyManua.ls Logo

Siemens 7SJ85 - Information List

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter C Setting Options Default Setting
_:32:6 Stage 2:Operate delay 0.00 s to 600.00 s 5.00 s
Information List
No. Information Data Class
(Type)
Type
General
_:2311:300 General:Undervoltage blocking SPS O
_:2311:301 General:f MV O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:31:81 Stage 1:>Block stage SPS I
_:31:54 Stage 1:Inactive SPS O
_:31:52 Stage 1:Behavior ENS O
_:31:53 Stage 1:Health ENS O
_:31:55 Stage 1:Pickup ACD O
_:31:56 Stage 1:Operate delay expired ACT O
_:31:57 Stage 1:Operate ACT O
Stage 2
_:32:81 Stage 2:>Block stage SPS I
_:32:54 Stage 2:Inactive SPS O
_:32:52 Stage 2:Behavior ENS O
_:32:53 Stage 2:Health ENS O
_:32:55 Stage 2:Pickup ACD O
_:32:56 Stage 2:Operate delay expired ACT O
_:32:57 Stage 2:Operate ACT O
6.32.6
Protection and Automation Functions
6.32 Overfrequency Protection
SIPROTEC 5, Overcurrent Protection, Manual 767
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals