EasyManua.ls Logo

Siemens 7SJ85 - Current-Unbalance Protection for Capacitors, 1-Phase

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Current-Unbalance Protection for Capacitors, 1-Phase
Setting Values for the Function
Automatic compensation Yes
No
Time between switch off and switch on 0.00 s to 60.00 s Increments of 0.01 s
Normalization with Ic Yes
No
Threshold of defective C-
element
1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 175.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Setting Values (Overcurrent-Protection Stage I>)
Current threshold I
unbal.
1 A @ 50 and 100 Irated 0.030 A to 35.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.150 A to 175.000 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.005 A
Operate delay 0.00 s to 60.00 s Increments of 0.01 s
Measured value compensated
non-compensated
Setting Values (Counter Stage)
Type of counting groups
segregated
sum
Type of counting phases segregated
sum
Max. no. of def. elem. phs A 1 to 1000 Increments of 1
Max. no. of def. elem. phs B 1 to 1000 Increments of 1
Max. no. of def. elem. phs C 1 to 1000 Increments of 1
Max. no. of def. elem. 1 to 1000 Increments of 1
Operate delay 0.00 s to 10000.00 s Increments of 0.01 s
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer 15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer 0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
12.26
Technical Data
12.26 Current-Unbalance Protection for Capacitors, 1-Phase
1502 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents