EasyManua.ls Logo

Siemens 7SJ85 - Analog-Units Function Group

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog-Units Function Group
20-mA Unit Ether. 7XV5674-0KK00-1AA1
Max. number of connected 20-mA units 4
Max. number of channels per 20-mA unit 12
20-mA Unit Serial 7XV5674-0KK30-1AA1 (RS485) and 7XV5674-0KK40-1AA1 (Fiberglass)
Max. number of connected 20-mA units 4
Max. number of channels per 20-mA unit 12
RTD Unit (Ziehl TR1200) 7XV5662-6AD10
Max. number of connected RTD units 4
Max. number of sensors per RTD unit 12
Sensor type Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.
RTD Unit (Ziehl TR1200 IP) 7XV5662-8AD10
Max. number of connected RTD units 4
Max. number of sensors per RTD unit 12
Sensor type Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.
Temperature Measured Values
Unit of measurement for temperature
°C or °F, adjustable
Pt 100 -199 °C to 800 °C (-326 °F to 1472 °F)
Ni 100 -54 °C to 278 °C (-65 °F to 532 °F)
Ni 120 -52 °C to 263 °C (-62 °F to 505 °F)
Resolution 1 °C or 1 °F
Tolerance ±0.5 % of the measured value ±1 K
12.4
Technical Data
12.4 Analog-Units Function Group
1420 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents